Functions and characteristics
Item No. | CNSD100-250 | CNSD400-630 | CNSD800-1600 | |
Number of poles | 3P, 4P | |||
Control | Manual | with toggle/with direct or extended rotary handle | ||
Connections | Fixed | front connections | ||
Plug-in | front connections/rear connections | |||
Electrical characteristics as per IEC60947 and EN60947-2 | ||||
Rated current(A) | In | 16,25,32,40,50,63,80,100,125,160,200,250 | 400,500,630 | 800, 1000, 1250, 1600 |
Rated insulation voltage(V) | Ui | 800 | ||
Rated impulse withstand voltage(kV) | Uimp | 8 | ||
Rated operational voltage(V) | Ue | AC 50/60Hz, 690V | ||
Utilization category | A | |||
Breaking capacity levels | F N H | N H | ||
Breaking capacity (kA rms) AC 50/60 Hz 380/415 V |
lcu | 36, 50, 70 | 50, 70 | |
Service breaking capacity (kA rms) AC 50/60 Hz 380/415 V |
lcs | 36, 50, 70 | 50, 70 | |
Operation performance | Mechanical | 20000 | 10000 | 10000 |
Electrical | 10000 | 5000 | 5000 | |
Protection | Chart B-1 B-2 | Chart C-1 | ||
Indication and control auxiliaries | ||||
Auxiliary switch | ■ | ■ | ||
MX Shunt coil | ■ | ■ | ||
MN under-voltage coil | ■ | ■ |
Protection
Overload protection: Thermal protection (lr)
Thermal overload protection based on a bimetal strip providing an inverse time curve l2t, corresponding to a temperature rise limit. Above this limit, the deformation of the strip trips the circuit breaker operating mechanism.
Overload protection has the following characteristics:
Anon-adjustable time delay.
Short-circuit protection: Magnetic protection (Im) Short-circuit protection with a fixed or adjustable pick-up lm that initiates instantaneous tripping if exceeded.
Protection of distribution system
Protection
Settings are made using the adjustment dials with fine adjustment possibilities.
Overload protection: long time protection(Ir)
Inverse time protection against overloads with an adjustable current pick-up lrsetusing a dial and a non-adjustable time delay tr.
Short-circuit protection: Short-time protection with fixed time delay(Isd)
Protection with an adjustable pick-up lsd.
Tripping takes place after a very short delay used to allow discrimination with the downstream device.
Short circuit instantaneous protection:(li)
lnstantaneous short-circuit protection with a fixed pick-up.
Protection
Chart C-1
Protection thresholds and delays are set using the adjustment dials.
Offer standard long time delay setting module.
overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Short-circuit protection
Short-time(rms) and instantaneous protection.
Selection of lt type(ON or OFF) for short-time delay.
Neutral protection
On 3-pole circuit breakers, neutral protection is not possible.
On 4-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5lr (4P 3d +N/2) or neutral protection at lr (4P 4d).
lndications
Overload indication by alarm LED on the front; the LED goes on when the current exceeds the long-time trip threshold.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.
Overall dimensions&Mounting dimensions
CNSD100 TO 250
TMD magnetic trip units,tripping curves protection of distribution systems
CNSD400 TO 630
CNSD500 TO 1600
lg=ln x... | A | B | C | D | E | F | G | H | J |
ln<400A | 0.3 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1 |
400A≤In≤1200A | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1 |
ln>1200A | 500 | 640 | 720 | 800 | 880 | 960 | 1040 | 1120 | 1200 |
Model | Qty/CTN(pcs) | GW(kg) | NW(kg) | Carton Size(cm) |
CNSD-100 3P | 12 | 21.5 | 29.2 | 42.5*40*24.5 |
CNSD-100 4P | 8 | 18.6 | 16.8 | 40.5*29*31 |
CNSD-160 3P | 12 | 22 | 19.7 | 42.5*40*24.5 |
CNSD-160 4P | 8 | 19.4 | 17.6 | 40.5*29*31 |
CNSD-250 3P | 12 | 24 | 21.5 | 42.5*40*24.5 |
CNSD-250 4P | 8 | 21 | 19.2 | 40.5*29*31 |
CNSD-400 3P | 4 | 24 | 21.5 | 33*31*30.5 |
CNSD-400 4P | 4 | 30.5 | 27.5 | 48.5*29.5*23 |
CNSD-630 3P | 4 | 24.8 | 22.3 | 33*31*30.5 |
CNSD-630 4P | 4 | 31.5 | 28.5 | 48.5*29.5*23 |
CNSD-800 3P | 1 | 14.1 | 12 | 45.5*35.5*31.5 |
CNSD-800 4P | 1 | 18.2 | 15.4 | 44.5*36*42.5 |
CNSD-1600 3P | 1 | 14.4 | 12.3 | 45.5*35.5*31.5 |
CNSD-1600 4P | 1 | 18.8 | 16 | 44.5*36*42.5 |
Today, we are pleased to introduce to you the different operating methods of molded case circuit breakers and their respective applicable scenarios. CNSX MCCB, as on...
Yueqing Shendian Electric Co., Ltd. are thrilled to announce that we will participate in the 49th Middle East Energy Dubai exhibition in the coming April. Middle Eas...
Nowruz, which translates to "New Day" in Persian, marks the beginning of the Persian calendar year and typically falls on the vernal equinox, usually around March 20...
The Spring Festival of 2024 has passed, and SSPD has resumed work as scheduled, filled with joy, abundant New Year blessings, and expectations. In this year full of ...